Wastewater/Activity/PacpInspection/1.0May 21, 2021, 06:48 AM
  • 18 0441_18 0440_05212021_000620.mp4

Date
05/20/2021
W/O
891049
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14292
Time
11:48 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8874
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_891049_TV18097_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0440
Downstream MH
18 0441
Dir. of Survey
Upstream
Length Surveyed
404.8 ft.
Total Length
404.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0440 to 18 0441
MH: 18 0440MH: 18 0441upstream0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 18 04410 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK7.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"27.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"280.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"303.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"353.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"377.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"400 ft. MGO - General Observation - HEAVY STEAM400 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start404.8 ft. AMH - Downstream Manhole, Survey Begins - 18 0440404.8 ft. MWM - Water Mark, 20 %of cross sectional area404.8 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
124.2TFC
4.8MGOHEAVY STEAM
152.9TFC
304.2TFC
4.8SAV
27.7TFC
51.3TFC
226.9TFC
404.8SAV
404.8AMH18 0441
0AMH18 0440
377TF
178.1TF
202.6TFC
397.4TFC
279.6TFC
351.6TFC
328TFC
404.8MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0MWL
101.2TFC
250.6TF

Properties (7)

additional_info
630138052021201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-20T23:48:13-07:00
documentation
PROPIPE
is_lateral_inspection
false