Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2021, 05:59 AM
  • 18 0437_18 0436_05202021_231700.mp4

Date
05/20/2021
W/O
891049
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14287
Time
10:59 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8874
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_891049_TV18097_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0437
Downstream MH
18 0436
Dir. of Survey
Downstream
Length Surveyed
405.4 ft.
Total Length
405.4 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
402
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
402
Pipe schematic from manhole 18 0437 to 18 0436
MH: 18 0437MH: 18 0436downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04370 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. MGO - General Observation - HEAVY STEAM8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"53 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"305 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"329 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"357.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"378.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"405 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0436405.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
0AMH18 0437
256TFC
405SSS
378.1TFC
179.2TFC
357.6TFC
53TFC
0MWM
126.4TFC
2.1SSS
3.8SAV
0MGOCONNECTION AT MH 9 O'CLOCK
102.2TFC
305TF
77.8TFC
329TF
405.4AMH18 0436
203.5TFC
24.3TFC
155.1TFC
0MWL
8TFC
280.6TFC
231.8TFC
3.8MGOHEAVY STEAM
405.4SAV

Properties (7)

additional_info
630138052021201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
2
customer
1
datetime
2021-05-20T22:59:53-07:00
documentation
PROPIPE
is_lateral_inspection
false