Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2021, 06:46 AM
  • 02 1837_02 1424_06102021_001208.mp4

Date
06/09/2021
W/O
890820
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02996
Time
11:46 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8893
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_890820_TV02317_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
33 in.
Upstream MH
02 1837
Downstream MH
02 1424
Dir. of Survey
Downstream
Length Surveyed
965 ft.
Total Length
965 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1837 to 02 1424
MH: 02 1837MH: 02 1424downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 18370 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0.3 ft. MWM - Water Mark, 25 %of cross sectional area2.2 ft. MGO - General Observation - MAG COAT330.3 ft. SAP - Surface Aggregate Projecting, at 12 o'clock, within 8 inches of joint: NO965 ft. AMH - Downstream Manhole, Survey Ends - 02 1424965 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (1)

  • Surface Aggregate Projecting, at 12 o'clock, within 8 inches of joint: NO

    330.3 ft. - Surface Aggregate Projecting, at 12 o'clock, within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
330.3SAP
965AMH02 1424
965MGOCONNECTION AT THE MH 9 OC'LOCK
0.3MWM
0AMH02 1837
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
2.2MGOMAG COAT

Properties (7)

additional_info
630074060921203
custom_field_three
no severe defects
custom_field_two
3
customer
1
datetime
2021-06-09T23:46:50-07:00
documentation
PROPIPE
is_lateral_inspection
false