Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 20, 2021, 09:24 AM
  • 01 0958_01 0957_05202021_023650.mp4

Date
05/20/2021
W/O
890942
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00228
PipeID
P01795
Time
2:24 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8964
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_890942_TV01251_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
36 in.
Upstream MH
01 0958
Downstream MH
01 0957
Dir. of Survey
Downstream
Length Surveyed
308.5 ft.
Total Length
308.5 ft.
Structural Index
2
Structural Quick
2C00
Structural Rating
38
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
42
Pipe schematic from manhole 01 0958 to 01 0957
MH: 01 0958MH: 01 0957downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 09580 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area25.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start36.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish54.5 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES56 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start95.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish171.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start199.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish276.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES305.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES308.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0957

Observation photos (6)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    25.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    54.5 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    56 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    171.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    276.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    305.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
36.3CL
308.5AMH01 0957
0AMH01 0958
171.9CL
199.9CL
95.8CL
276.5CL
56CL
305.1CL
0MWM
54.5CS
0MWL
25.6CL

Properties (7)

custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-05-20T02:24:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286