Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 07:59 AM
  • 01 0976_01 0975_05192021_011306.mp4

Date
05/19/2021
W/O
890942
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00228
PipeID
P01814
Time
12:59 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8963
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_890942_TV01251_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
33 in.
Upstream MH
01 0975
Downstream MH
01 0976
Dir. of Survey
Upstream
Length Surveyed
333.7 ft.
Total Length
333.7 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 01 0975 to 01 0976
MH: 01 0975MH: 01 0976upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - 01 09760 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish235.2 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES - .244.1 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES - .329.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start333.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK333.7 ft. AMH - Downstream Manhole, Survey Begins - 01 0975333.7 ft. MWL - Water Level, 15 %of cross sectional area333.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK333.7 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Localized Liner, within 8 inches of joint: YES - .

    89.6 ft. - Repair Localized Liner, within 8 inches of joint: YES - .

  • Repair Localized Liner, within 8 inches of joint: YES - .

    98.5 ft. - Repair Localized Liner, within 8 inches of joint: YES - .

Observations (12)

DistanceCodeObservation
98.5RPL.
333.7MGOCONNECTION AT THE MH 9 OC'LOCK
333.7MGOCONNECTION AT THE MH 3 OC'LOCK
333.7AMH01 0976
0MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH01 0975
4.5CM
0MWL
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
89.6RPL.
333.7CM

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-19T00:59:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false