Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 07:39 AM
  • 01 0975_01 0974_05192021_005738.mp4

Date
05/19/2021
W/O
890942
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00228
PipeID
P01813
Time
12:39 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8963
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_890942_TV01251_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
33 in.
Upstream MH
01 0974
Downstream MH
01 0975
Dir. of Survey
Upstream
Length Surveyed
332.3 ft.
Total Length
332.3 ft.
Structural Index
2
Structural Quick
332G
Structural Rating
89
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
89
Pipe schematic from manhole 01 0974 to 01 0975
MH: 01 0974MH: 01 0975upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - 01 09750 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK9.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish9.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES35.7 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES37.4 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES48.2 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES123.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start126.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES129.7 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES129.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES152.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES196.8 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Finish232.4 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Start306.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES312 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES314.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES319 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES328.3 ft. CS - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES332.3 ft. AMH - Downstream Manhole, Survey Begins - 01 0974332.3 ft. MWL - Water Level, 15 %of cross sectional area332.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK332.3 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (15)

  • Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    13.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    17.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    20.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    26.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Water Level, Sag in pipe, 15 %of cross sectional area, Start

    99.9 ft. - Water Level, Sag in pipe, 15 %of cross sectional area, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    180.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    202.6 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    202.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    205.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    208.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    284.1 ft. - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    294.9 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    296.6 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    322.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
202.6CM
284.1CS
4CS
208.9CL
322.6CL
180.1CM
0AMH01 0974
26.1CL
294.9CS
332.3MGOCONNECTION AT THE MH 9 OC'LOCK
135.5MWLS
99.9MWLS
0MWL
202.6CL
322.6CM
0MGOCONNECTION AT THE MH 9 OC'LOCK
296.6CS
205.6CL
332.3AMH01 0975
13.3CL
20.3CL
332.3MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
17.8CL

Properties (6)

custom_field_three
MULTIPLE CRACKS, SAG
custom_field_two
3
customer
1
datetime
2021-05-19T00:39:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false