Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 08:26 AM
  • 01 0974_01 0973_05192021_014027.mp4

Date
05/19/2021
W/O
890942
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00228
PipeID
P01812
Time
1:26 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8963
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_890942_TV01251_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
33 in.
Upstream MH
01 0974
Downstream MH
01 0973
Dir. of Survey
Downstream
Length Surveyed
330.2 ft.
Total Length
330.2 ft.
Structural Index
2
Structural Quick
312H
Structural Rating
89
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
93
Pipe schematic from manhole 01 0974 to 01 0973
MH: 01 0974MH: 01 0973downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 09740 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK44.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"58.1 ft. CS - Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES91.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES99.9 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES118.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES131.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES135.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start170.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"330.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK330.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0973330.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

    58.1 ft. - Crack Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    91.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    99.9 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    118.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    131.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    135.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

    170.1 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"

Observations (15)

DistanceCodeObservation
330.2MGOCONNECTION AT THE MH 3 OC'LOCK
330.2AMH01 0973
0AMH01 0974
91.6CL
0MWM
135.2CL
330.2CL
99.9CM
58.1CS
131.5CL
0MWL
170.1TB
118.4CL
0MGOCONNECTION AT THE MH 3 OC'LOCK
44.3TFC

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-19T01:26:55-07:00
documentation
PRO PIPE
is_lateral_inspection
false