Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 08:47 AM
  • 01 0972_01 0971A_05192021_015930.mp4

Date
05/19/2021
W/O
890942
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00228
PipeID
P01810
Time
1:47 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8963
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_890942_TV01251_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
33 in.
Upstream MH
01 0972
Downstream MH
01 0971A
Dir. of Survey
Downstream
Length Surveyed
356.7 ft.
Total Length
356.7 ft.
Structural Index
3
Structural Quick
3L24
Structural Rating
197
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
197
Pipe schematic from manhole 01 0972 to 01 0971A
MH: 01 0972MH: 01 0971Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 09720 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area25.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES28.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start43.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish43.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start356.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK356.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK356.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0971A

Observation photos (3)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    25.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    28.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    43.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
356.7CM
356.7MGOCONNECTION AT THE MH 3 OC'LOCK
356.7MGOCONNECTION AT THE MH 9 OC'LOCK
356.7AMH01 0971A
0AMH01 0972
28.5CL
43.4CL
0MWL
0MWM
43.5CM
25.7CL

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-19T01:47:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false