Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2021, 09:55 AM
  • 08 0493A_08 0493_6102021_033814.mp4

Date
06/10/2021
W/O
0890878
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00552
Time
2:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1840
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20210610MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0493A
Downstream MH
08 0493
Dir. of Survey
Downstream
Length Surveyed
279.6 ft.
Total Length
279.6 ft.
Structural Index
2
Structural Quick
3328
Structural Rating
25
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
27
Pipe schematic from manhole 08 0493A to 08 0493
MH: 08 0493AMH: 08 0493downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area12.2 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SLIGHT12.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES22.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL33.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE33.5 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL42 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H52.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H57.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINMTS57.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS57.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS57.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS73.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped76.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped103.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start124.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped127.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped171.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped174.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped222.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped225.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped268.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8" - Capped272 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped279 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish279 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 30% SLIGHT AT JOINTS279 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 5%SLIGHT AT JOINTS279 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 560% SLIGHT AT JOINTS279 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS279.6 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    103.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (32)

DistanceCodeObservation
12.2FCSLIGHT
279DAGS
57.3FLHAIRLINE AT JOINMTS
268.7TFCCapped
52.4FCH
33.5FCHAIRLINE
279FC30% SLIGHT AT JOINTS
57.3FLSLIGHT AT JOINTS
279FL5%SLIGHT AT JOINTS
279FC560% SLIGHT AT JOINTS
103.2DAGS
174.4TFCCapped
124.9TFCCapped
22.2FCSL
57.3FCHAIRLINE AT JOINTS
42FCH
272TFCCapped
12.2FL
127.5TFCCapped
76.7TFCCapped
57.3FCSLIGHT AT JOINTS
225.4TFCCapped
279.6AMH4:10AM
0MWM
171.9TFCCapped
279FL10% SLIGHT AT JOINTS
33.5FCSL
73.9TFCCapped
222.4TFCCapped
0AMH3:40AM
0MGOConn. @ Mh, 9 O' Clock. Active
0MWL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-06-10T02:55:37-07:00
documentation
MARTIN,OLIVER 111,RAMIREZ
is_lateral_inspection
false