Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2021, 09:57 AM
  • H 0560_H 0559_05212021_031851.mp4

Date
05/21/2021
W/O
890859
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00186
PipeID
P10984
Time
2:57 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8921
Sewer Name
H JOINT OUTFALL H - UNIT 8C
City
BALDWIN PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_890859_TV15170_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0560
Downstream MH
H 0559
Dir. of Survey
Downstream
Length Surveyed
450.5 ft.
Total Length
450.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
4132
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole H 0560 to H 0559
MH: H 0560MH: H 0559downstream0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05602 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING THROUGHOUT19 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start56.7 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES58 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"82 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR82.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.7 ft. RMC - Roots Medium Connection, from 07 to 11 o'clock, 15 %, within 8 inches of joint: YES171.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"179 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.3 ft. RFC - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES235.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"243.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE280.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK280.9 ft. MGO - General Observation - UNMAPPED MH291.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"348.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"395.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"404 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"427.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"448.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish448.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish450.5 ft. AMH - Downstream Manhole, Survey Ends - H 0559450.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (11)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

    56.7 ft. - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    58 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    171.4 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

    227.3 ft. - Roots Fine Connection, from 01 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    280.9 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - UNMAPPED MH

    280.9 ft. - General Observation - UNMAPPED MH

  • General Observation - COCKROACHES IN MANHOLE

    450.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (39)

DistanceCodeObservation
19SAV
58TFA
450.5AMHH 0559
235.1TFC
82.2TFA
169.7RMC
211.3TFC
194.9TFC
154.5TFC
448.6DAGS
243.3TF
56.7RMC
339.8TFC
203.2TFC
448.6SAV
163.2TFC
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0MWL
179TFA
2DAGS
404TFA
450.5MGOCOCKROACHES IN MANHOLE
291.6TFA
427.7TFA
0MGOCOCKROACHES IN MANHOLE
395.7TFA
219.6TFC
2MGOMAG COATING THROUGHOUT
122.3TFA
171.4TFA
82RFJ
227.3TFA
280.9MGOCOCKROACHES IN MANHOLE
0MWM
280.9MGOCONNECTION AT MH 9 O'CLOCK
0AMHH 0560
227.3RFC
348.1TFA
280.9MGOUNMAPPED MH

Properties (7)

additional_info
630069052021201
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2021-05-21T02:57:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false