- Date
- 05/20/2021
- W/O
- 890859
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00186
- PipeID
- P10981
- Time
- 11:13 PM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8921
- Sewer Name
- H JOINT OUTFALL H - UNIT 8C
- City
- BALDWIN PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 24
- Purpose
- Routine Assessment
- Project
- WO_890859_TV15170_MAY2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Width
- 30 in.
- Upstream MH
- H 0557
- Downstream MH
- H 0556
- Dir. of Survey
- Downstream
- Length Surveyed
- 229.2 ft.
- Total Length
- 229.2 ft.
- Structural Index
- 3
- Structural Quick
- 3H00
- Structural Rating
- 132
- O&M Index
- 2
- O&M Quick
- 2H00
- O&M Rating
- 90
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 222
Pipe schematic from manhole H 0557 to H 0556 Observation photos (4)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - General Observation - MAG COATING THROUGHOUT

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start