Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2021, 07:00 AM
  • H 0553_H 0552_05212021_010711.mp4

Date
05/21/2021
W/O
890859
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00186
PipeID
P10977
Time
12:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8921
Sewer Name
H JOINT OUTFALL H - UNIT 8C
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_890859_TV15170_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0553
Downstream MH
H 0552
Dir. of Survey
Downstream
Length Surveyed
307.3 ft.
Total Length
307.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
162
O&M Index
2
O&M Quick
4112
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
168
Pipe schematic from manhole H 0553 to H 0552
MH: H 0553MH: H 0552downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 05530 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area35.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start55.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"62.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.8 ft. RFC - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: YES158.1 ft. RFC - Roots Fine Connection, from 03 to 02 o'clock, within 8 inches of joint: YES158.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.3 ft. MWL - Water Level, 55 %of cross sectional area264.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.1 ft. MWL - Water Level, 50 %of cross sectional area304.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish306.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK307.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE307.3 ft. AMH - Downstream Manhole, Survey Ends - H 0552

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    35.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Connection, at 02 o'clock, within 8 inches of joint: YES

    155.8 ft. - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, from 03 to 02 o'clock, within 8 inches of joint: YES

    158.1 ft. - Roots Fine Connection, from 03 to 02 o'clock, within 8 inches of joint: YES

  • Water Level, 55 %of cross sectional area

    226.3 ft. - Water Level, 55 %of cross sectional area

  • General Observation - COCKROACHES IN MANHOLE

    307.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (24)

DistanceCodeObservation
264.1TFC
306.4MGOCONNECTION AT MH 3 O'CLOCK
307.3MGOCOCKROACHES IN MANHOLE
155.8TBA
0MGOCOCKROACHES IN MANHOLE
158.1RFC
158.1TBA
0AMHH 0553
127.8TFC
0MGOCONNECTION AT MH 3 O'CLOCK
159.4TFA
35.5SAV
226.3MWL
0MWM
307.3AMHH 0552
0MWL
155.8RFC
216.5TFA
304.2SAV
55.4TF
62.8TFC
119.8TFA
192.9TFA
264.1MWL

Properties (7)

additional_info
630069052021201
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2021-05-21T00:00:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false