Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2021, 10:28 AM
  • 21 0391_21 0390_05142021_034419.mp4

Date
05/14/2021
W/O
891471
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00757
PipeID
P15597
Time
3:28 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8957
Sewer Name
21 CENTER STREET TRUNK
City
WEST COVINA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
WO_891471_TV21124_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
21 0391
Downstream MH
21 0390
Dir. of Survey
Downstream
Length Surveyed
353.1 ft.
Total Length
353.1 ft.
Structural Index
2
Structural Quick
4133
Structural Rating
22
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
23
Pipe schematic from manhole 21 0391 to 21 0390
MH: 21 0391MH: 21 0390downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 21 039132.2 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES38.4 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES74.7 ft. JOM - Joint Offset Medium89.9 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES97 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES126.1 ft. CM - Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES132.4 ft. CS - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES151.3 ft. CS - Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES175.8 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES267.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES275.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"353.1 ft. AMH - Downstream Manhole, Survey Ends - 21 0390

Observation photos (10)

  • Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    32.2 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

    38.4 ft. - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    74.7 ft. - Joint Offset Medium

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    89.9 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    97 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES

    126.1 ft. - Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    132.4 ft. - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

    151.3 ft. - Crack Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    175.8 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    267.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
132.4CS
32.2CS
126.1CM
38.4CM
0MWM
97FM
0MWL
275.2TFC
175.8CS
267.1RFJ
151.3CS
74.7JOM
0MGOCONNECTION AT MH, 9 O'CLOCK
353.1AMH21 0390
89.9CM
0AMH21 0391

Properties (6)

custom_field_three
MULTIPLE CRACKS, OFFSET. FRACTURES
custom_field_two
3
customer
1
datetime
2021-05-14T03:28:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false