Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2021, 11:44 AM
  • 15 0062_15 0061_05172021_050457.mp4

Date
05/17/2021
W/O
891123
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11956
Time
4:44 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8914
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_891123_TV15220_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0062
Downstream MH
15 0061
Dir. of Survey
Downstream
Length Surveyed
414.1 ft.
Total Length
414.1 ft.
Structural Index
4
Structural Quick
5133
Structural Rating
14
O&M Index
2
O&M Quick
422O
O&M Rating
172
Overall Index
2
Overall Quick
Overall Rating
186
Pipe schematic from manhole 15 0062 to 15 0061
MH: 15 0062MH: 15 0061downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00622 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start23.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES50.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish223.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start227.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"296.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"357.5 ft. MWM - Water Mark, 60 %of cross sectional area357.5 ft. MWL - Water Level, 40 %of cross sectional area382.1 ft. HVV - Hole Void Visible, from 10 to 02 o'clock, within 8 inches of joint: YES388.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES403.5 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES411.2 ft. MWL - Water Level, 20 %of cross sectional area411.2 ft. MWM - Water Mark, 50 %of cross sectional area412.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Finish414.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0061414.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK414.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    24.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES, Start

    223.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start

  • Hole Void Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    382.1 ft. - Hole Void Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    388.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    403.5 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    414.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (33)

DistanceCodeObservation
357.5MWM
414.1AMH15 0061
251.7TFC
0MGOCOCKROACHES IN MANHOLE
24.8CM
298.6TFC
357.5MWL
278.1TF
223.6DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
414.1MGOCONNECTION AT MH 9 O'CLOCK
124.2TFC
0MWM
175.2TFC
0MWL
382.1HVV
388.8CM
0AMH15 0062
151.4TF
227.6TFC
23.8TFC
223.6DAGS
411.2MWL
414.1MGOCOCKROACHES IN MANHOLE
296.3TBA
201.3TFC
100.8TFC
411.2MWM
403.5FS
2DAGS
74.2TFC
50.4TFC
412.1DAGS

Properties (7)

additional_info
630069051721004
custom_field_three
HOLE IN PIPE/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-05-17T04:44:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false