Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2021, 11:02 AM
  • 15 1044_15 0060_05172021_041154.mp4

Date
05/17/2021
W/O
891123
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11955
Time
4:02 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8914
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_891123_TV15220_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 1044
Downstream MH
15 0060
Dir. of Survey
Downstream
Length Surveyed
147.1 ft.
Total Length
147.1 ft.
Structural Index
3
Structural Quick
513B
Structural Rating
56
O&M Index
2
O&M Quick
2E00
O&M Rating
58
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 15 1044 to 15 0060
MH: 15 1044MH: 15 0060downstream0 ft. MGO - General Observation - CONNECTION AT MH 10 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 10440 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start60.6 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES66.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start102.8 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES144.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish144.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish147.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0060147.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    60.6 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    66.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

    102.8 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    147.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
66.9CM
60.6CM
147.1AMH15 0060
102.8B
144.8CM
0MGOCONNECTION AT MH 10 O'CLOCK
0AMH15 1044
0MWM
0MWL
147.1MGOCOCKROACHES IN MANHOLE
2DAGS
144.8DAGS

Properties (7)

additional_info
630069051721004
custom_field_three
BROKEN PIPE/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-05-17T04:02:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false