Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2021, 11:25 AM
  • 15 0060_15 0059A_05172021_043204.mp4

Date
05/17/2021
W/O
891123
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11954
Time
4:25 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8914
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_891123_TV15220_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0060
Downstream MH
15 0059A
Dir. of Survey
Downstream
Length Surveyed
11.8 ft.
Total Length
11.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 15 0060 to 15 0059A
MH: 15 0060MH: 15 0059Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 00600 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES10.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES10.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish11.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE11.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0059A

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    8.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    10.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    11.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
10.8DAGS
2DAGS
0AMH15 0060
10.1CM
8.5CL
11.8MGOCOCKROACHES IN MANHOLE
0MWM
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
11.8AMH15 0059A

Properties (7)

additional_info
630069051721004
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-05-17T04:25:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false