Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 20, 2021, 06:28 AM
  • H 0434_H 0433_05192021_233843.mp4

Date
05/19/2021
W/O
890833
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00180
PipeID
P10889
Time
11:28 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8919
Sewer Name
H JOINT OUTFALL H - UNIT 5D
City
SOUTH EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_890833_TV15196_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 0434
Downstream MH
H 0433
Dir. of Survey
Downstream
Length Surveyed
158.6 ft.
Total Length
158.6 ft.
Structural Index
2
Structural Quick
2C00
Structural Rating
44
O&M Index
2
O&M Quick
2E00
O&M Rating
62
Overall Index
2
Overall Quick
Overall Rating
106
Pipe schematic from manhole H 0434 to H 0433
MH: H 0434MH: H 0433downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04340 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start49 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start156.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish156.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish158.6 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK158.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE158.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK158.6 ft. AMH - Downstream Manhole, Survey Ends - H 0433

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    49 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    158.6 ft. - General Observation - COCKROACHES IN MANHOLE

  • Downstream Manhole, Survey Ends - H 0433

    158.6 ft. - Downstream Manhole, Survey Ends - H 0433

Observations (13)

DistanceCodeObservation
49SSS
156.9SSS
2MGOMAG COATING THROUGHOUT
0MWM
158.6MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0MWL
2DAGS
158.6MGOCOCKROACHES IN MANHOLE
158.6MGOCONNECTION AT MH 9 O'CLOCK
158.6AMHH 0433
156.9DAGS
0AMHH 0434
0MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
630069051921202
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-05-19T23:28:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false