Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2021, 05:28 AM
  • 05 2265_05 2264A_05242021_225117.mp4

Date
05/24/2021
W/O
890873
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00546
PipeID
P07391
Time
10:28 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8967
Sewer Name
05 104TH STREET TRUNK
City
LENNOX
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_890873_TV05347_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
10 in.
Upstream MH
05 2265
Downstream MH
05 2264A
Dir. of Survey
Downstream
Length Surveyed
327.6 ft.
Total Length
327.6 ft.
Structural Index
3
Structural Quick
3421
Structural Rating
14
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 05 2265 to 05 2264A
MH: 05 2265MH: 05 2264Adownstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 22650 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area6.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES10.9 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES12.8 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: NO12.8 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"74.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"128.2 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"151.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES178.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"223.2 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"268.8 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES268.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"306.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"327.6 ft. AMH - Downstream Manhole, Survey Ends - 05 2264A ABANDONED MANHOLE

Observation photos (13)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    10.9 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: NO

    12.8 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: NO

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    12.8 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    74.7 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    128.2 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    151.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    178.6 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    223.2 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    268.8 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    268.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    306.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Downstream Manhole, Survey Ends - 05 2264A ABANDONED MANHOLE

    327.6 ft. - Downstream Manhole, Survey Ends - 05 2264A ABANDONED MANHOLE

Observations (17)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH05 2265
10.9CM
268.8CS
0MWL
6.5CM
74.7TBC
12.8CM
12.8TBC
223.2TBC
151.8CM
268.8TB
0MWM
128.2TBC
178.6TBC
306.3TB
327.6AMH05 2264A ABANDONED MANHOLE

Properties (6)

custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-05-24T22:28:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false