Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2021, 07:19 AM
  • 05 2262_05 0300_05252021_002516.mp4

Date
05/25/2021
W/O
890873
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00546
PipeID
P07388
Time
12:19 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8967
Sewer Name
05 104TH STREET TRUNK
City
LENNOX
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_890873_TV05347_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
10 in.
Upstream MH
05 2262
Downstream MH
05 0300
Dir. of Survey
Downstream
Length Surveyed
47.5 ft.
Total Length
47.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 2262 to 05 0300
MH: 05 2262MH: 05 0300downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 22620 ft. MWM - Water Mark, 35 %of cross sectional area39.4 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES43.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES46.8 ft. DAR - Deposits Attached Ragging, 20 %of cross sectional area, from 05 to 09 o'clock, , within 8 inches of joint: YES47.4 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK47.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0300

Observation photos (3)

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    39.4 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    43.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Ragging, 20 %of cross sectional area, from 05 to 09 o'clock,  , within 8 inches of joint: YES

    46.8 ft. - Deposits Attached Ragging, 20 %of cross sectional area, from 05 to 09 o'clock, , within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0MWL
47.5AMH05 0300
0AMH05 2262
43.3CM
46.8DAR
39.4FS
0MWM
47.4MGOCONNECTION AT THE MH 12 OC'LOCK

Properties (6)

custom_field_three
cracks
custom_field_two
3
customer
1
datetime
2021-05-25T00:19:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false