Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2021, 08:42 AM
  • 18 0915_18 0914_05272021_020052.mp4

Date
05/27/2021
W/O
890877
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00709
PipeID
P14766
Time
1:42 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8928
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_890877_TV18049_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0915
Downstream MH
18 0914
Dir. of Survey
Downstream
Length Surveyed
453.9 ft.
Total Length
453.9 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
270
O&M Index
2
O&M Quick
2Q00
O&M Rating
180
Overall Index
3
Overall Quick
Overall Rating
450
Pipe schematic from manhole 18 0915 to 18 0914
MH: 18 0915MH: 18 0914downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 18 09150 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start450 ft. MGO - General Observation - SPALLING THROUGHOUT450.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish450.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish453.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0914453.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • General Observation - MAG COATING THROUGHOUT

    0 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    453.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
450MGOSPALLING THROUGHOUT
0MWM
453.9AMH18 0914
450.8SAP
453.9MGOCOCKROACHES IN MANHOLE
0MWL
450.8DAGS
2DAGS
0MGOCOCKROACHES IN MANHOLE
0AMH18 0915
2SAP
0MGOMAG COATING THROUGHOUT

Properties (7)

additional_info
630069052621201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-05-27T01:42:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false