Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2021, 06:38 AM
  • 18 0865_18 0864_05272021_001005.mp4

Date
05/26/2021
W/O
890877
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00709
PipeID
P14717
Time
11:38 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8928
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
WO_890877_TV18049_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0865
Downstream MH
18 0864
Dir. of Survey
Downstream
Length Surveyed
520.8 ft.
Total Length
520.8 ft.
Structural Index
3
Structural Quick
3T2T
Structural Rating
515
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
519
Pipe schematic from manhole 18 0865 to 18 0864
MH: 18 0865MH: 18 0864downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 18 08650 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - POSSIBLE SPALLING2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start519 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - POSSIBLE SPALLING519.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish519.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK520.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0864

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
0AMH18 0865
520.8AMH18 0864
0MWM
2SSSPOSSIBLE SPALLING
2MGOMAG COATING THROUGHOUT
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
2SAP
519SSSPOSSIBLE SPALLING
519.1SAP
519.1MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630069052621201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-05-26T23:38:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false