Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2021, 09:05 AM
  • 18 0846_18 0845_652021_022005.mp4

Date
06/05/2021
W/O
0890824
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14701
Time
2:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1831
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Capital Improvement Program Assesment
Project
20210603MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
18 0846
Downstream MH
18 0845
Dir. of Survey
Downstream
Length Surveyed
331.8 ft.
Total Length
331.8 ft.
Structural Index
4
Structural Quick
4621
Structural Rating
26
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
30
Pipe schematic from manhole 18 0846 to 18 0845
MH: 18 0846MH: 18 0845downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM2 ft. MGO - General Observation - MAG COAT60% START2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SAM - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG32 ft. SAM - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG65.5 ft. SAM - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG116.3 ft. MGO - General Observation - 70% MAG COAT168.6 ft. SAM - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG272.1 ft. SAM - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Change - SEVERE AGG331.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE331.1 ft. SAM - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG331.1 ft. SAM - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG331.8 ft. AMH - Downstream Manhole, Survey Ends - 2:55AM

Observation photos (9)

  • General Observation - MAG COAT60% START

    2 ft. - General Observation - MAG COAT60% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

    32 ft. - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    65.5 ft. - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 70% MAG COAT

    116.3 ft. - General Observation - 70% MAG COAT

  • Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

    168.6 ft. - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Change - SEVERE AGG

    272.1 ft. - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Change - SEVERE AGG

Observations (16)

DistanceCodeObservation
2MGOMAG COAT60% START
331.1SSSBLISTERING PEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE
65.5SAMSEVERE AGG
2SAMSEVERE AGG
0MWM
0MWL
116.3MGO70% MAG COAT
2SAMSEVERE AGG
272.1SAMSEVERE AGG
331.8AMH2:55AM
32SAMSEVERE AGG
331.1SAMSEVERE AGG
168.6SAMSEVERE AGG
0AMH2:20AM
331.1SAMSEVERE AGG

Properties (5)

custom_field_two
3SEVERE AGG MISSING
customer
LACSD
datetime
2021-06-05T02:05:28-07:00
documentation
MARTIN,OLIVER 111,BARR,RAMIREZ
is_lateral_inspection
false