Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2021, 11:18 AM
  • 18 0850_18 0849_642021_042224.mp4

Date
06/04/2021
W/O
0890824
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14705
Time
4:18 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1831
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Capital Improvement Program Assesment
Project
20210603MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
18 0850
Downstream MH
18 0849
Dir. of Survey
Downstream
Length Surveyed
54.7 ft.
Total Length
54.7 ft.
Structural Index
3
Structural Quick
4231
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 18 0850 to 18 0849
MH: 18 0850MH: 18 0849downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVBERE AGG2 ft. SAM - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG54.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE54.1 ft. SAM - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG54.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN54.1 ft. SAM - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG54.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG54.7 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (4)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVBERE AGG

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVBERE AGG

  • Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

Observations (15)

DistanceCodeObservation
54.7AMH4:35AM
54.1SSSBLISTERING PEELING CONCRETE
2SAVSEVBERE AGG
0MWL
0MWL
0MGOConn. @ Mh, 3 O' Clock. Active
54.1SAMSEVERE AGG
0MWM
2SAMSEVERE AGG
54.1MGOConn. @ Mh, 3 O' Clock. OPEN
2SSSBLISTERING PEELING CONCRETE
54.1SAMSEVERE AGG
0AMH4:25AM
54.1SAVSEVERE AGG
2SAMSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2021-06-04T04:18:21-07:00
documentation
MARTIN,OLIVER 111,BARR,RAMIREZ
is_lateral_inspection
false