Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2021, 09:35 AM
  • 08 0533_08 0532_622021_024104.mp4

Date
06/02/2021
W/O
0890878
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00595
Time
2:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1828
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210602MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0532
Downstream MH
08 0533
Dir. of Survey
Upstream
Length Surveyed
242.2 ft.
Total Length
242.2 ft.
Structural Index
2
Structural Quick
312B
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
37
Pipe schematic from manhole 08 0532 to 08 0533
MH: 08 0532MH: 08 0533upstream0 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM85.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - FLAKING OUTER LAYER129 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL132.9 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H137.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H161.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL165.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL165.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL173.4 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - H177.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H180.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL185.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H204.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H209.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H213.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H224.9 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - H229 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL233 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT236.7 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE242.2 ft. AMH - Downstream Manhole, Survey Begins - 2:40AM242.2 ft. MWM - Water Mark, 20 %of cross sectional area242.2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - FLAKING OUTER LAYER

    157 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - FLAKING OUTER LAYER

Observations (22)

DistanceCodeObservation
33FCH
77.1FCSL
13.2FCSL
0AMH2:40AM
157SSSFLAKING OUTER LAYER
61.5FCSL
5.5FCHAIRLINE
17.3FCH
65.1FCH
68.8FCH
29.1FCH
0MWM
37.3FLH
242.2AMH3:05AM
77.1FCSL
0MWL
113.2FCSL
9.2FCSLIGHT
109.3FCH
81FCSL
57.1FCH
104.9FCH

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-06-02T02:35:35-07:00
documentation
MARTIN,BARR,RAMIREZ
is_lateral_inspection
false