Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2021, 08:57 AM
  • 08 0532_08 0531_622021_020907.mp4

Date
06/02/2021
W/O
0890878
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00594
Time
1:57 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1828
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210602MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0531
Downstream MH
08 0532
Dir. of Survey
Upstream
Length Surveyed
198.2 ft.
Total Length
198.2 ft.
Structural Index
2
Structural Quick
2500
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 08 0531 to 08 0532
MH: 08 0531MH: 08 0532upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:30AM8.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H8.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL28.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT125.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE185.4 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES - SLIGHT198.2 ft. MWM - Water Mark, 30 %of cross sectional area198.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active198.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active198.2 ft. MWL - Water Level, 10 %of cross sectional area198.2 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM

Observations (11)

DistanceCodeObservation
190FCH
0MWM
12.8FCSLIGHT
190FCSL
0MGOConn. @ Mh, 3 O' Clock. Active
0MGOConn. @ Mh, 9 O' Clock. Active
169.8FCSLIGHT
198.2AMH2:30AM
73.1FCHAIRLINE
0MWL
0AMH2:10AM

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-06-02T01:57:53-07:00
documentation
MARTIN,BARR,RAMIREZ
is_lateral_inspection
false