Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 05:07 AM
  • 18 0365_18 0364_05182021_221902.mp4

Date
05/18/2021
W/O
890902
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14199
Time
10:07 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8869
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_890902_TV18060_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0365
Downstream MH
18 0364
Dir. of Survey
Downstream
Length Surveyed
308.2 ft.
Total Length
308.2 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
308
O&M Index
2
O&M Quick
412K
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
434
Pipe schematic from manhole 18 0365 to 18 0364
MH: 18 0365MH: 18 0364downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 03650 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN126.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"228.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES274.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"306 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish306 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish306 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish308 ft. MGO - General Observation - ROACHES @ MH308.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED308.2 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE308.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0364

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    228.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
126.8TFC
0AMH18 0365
0MWL
274.6TFC
308.2MGOCONN @ MH 9 O'CLOCK/CAPPED
306SSS
0MGOCONN @ MH 3 O'CLOCK/CAPPED
53.3TFOPEN
308.2MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWM
228.7CM
0MGOROACHES @ MH
308MGOROACHES @ MH
308.2AMH18 0364
2SSS
0MGOCONN @ MH 9 O'CLOCK/CAPPED
306DAGS
306CM
226.9TFC
2DAGS
2CM

Properties (7)

additional_info
630138051821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-18T22:07:48-07:00
documentation
PROPIPE
is_lateral_inspection
false