Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 07:08 AM
  • 18 0361_18 0360_05192021_001556.mp4

Date
05/19/2021
W/O
890902
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14195
Time
12:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8869
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_890902_TV18060_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0361
Downstream MH
18 0360
Dir. of Survey
Downstream
Length Surveyed
201.3 ft.
Total Length
201.3 ft.
Structural Index
3
Structural Quick
413G
Structural Rating
204
O&M Index
2
O&M Quick
412G
O&M Rating
82
Overall Index
2
Overall Quick
Overall Rating
286
Pipe schematic from manhole 18 0361 to 18 0360
MH: 18 0361MH: 18 0360downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 03610 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0 ft. MWL - Water Level, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"19.3 ft. FM - Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES24 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES80.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN128.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"199 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish199 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish201 ft. MGO - General Observation - ROACHES @ MH201.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish201.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0360201.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

    19.3 ft. - Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    24 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
199SSS
201.3CM
80.4TFOPEN
24CL
0MGOROACHES @ MH
17.4TFC
0AMH18 0361
2DAGS
201.3AMH18 0360
2CM
128.7TFC
0MWM
0MGOCONN @ MH 3 O'CLOCK/OPEN
199DAGS
19.3FM
0MWL
2SSS
171.8TFC
201.3MGOCONN @ MH 3 O'CLOCK/CAPPED
201MGOROACHES @ MH

Properties (7)

additional_info
630138051821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-19T00:08:13-07:00
documentation
PROPIPE
is_lateral_inspection
false