Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 07:25 AM
  • 18 0359_18 0358_05192021_003101.mp4

Date
05/19/2021
W/O
890902
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14193
Time
12:25 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8869
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_890902_TV18060_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0359
Downstream MH
18 0358
Dir. of Survey
Downstream
Length Surveyed
86 ft.
Total Length
86 ft.
Structural Index
2
Structural Quick
3B2B
Structural Rating
77
O&M Index
2
O&M Quick
412B
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
113
Pipe schematic from manhole 18 0359 to 18 0358
MH: 18 0359MH: 18 0358downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03590 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start83 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish83 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish86 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED86 ft. AMH - Downstream Manhole, Survey Ends - 18 035886 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED86 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
86MGOCONN @ MH 9 O'CLOCK/CAPPED
86AMH18 0358
0MGOCONN @ MH 3 O'CLOCK/CAPPED
83DAGS
86MGOCONN @ MH 3 O'CLOCK/CAPPED
2SSS
2DAGS
9.2CM
83SSS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MGOROACHES @ MH
0MWL
86CM
0AMH18 0359
0MWM

Properties (7)

additional_info
630138051821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-19T00:25:09-07:00
documentation
PROPIPE
is_lateral_inspection
false