Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2021, 07:31 AM
  • 18 0358_18 0357_05192021_004506.mp4

Date
05/19/2021
W/O
890902
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14192
Time
12:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8869
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_890902_TV18060_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0358
Downstream MH
18 0357
Dir. of Survey
Downstream
Length Surveyed
246.6 ft.
Total Length
246.6 ft.
Structural Index
3
Structural Quick
3I2I
Structural Rating
246
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
342
Pipe schematic from manhole 18 0358 to 18 0357
MH: 18 0358MH: 18 0357downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03582 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN49 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES100 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN141.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"195 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN244 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish244 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish246 ft. MGO - General Observation - ROACHES @ MH246.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED246.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish246.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED246.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0357

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    49 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0MGOCONN @ MH 3 O'CLOCK/CAPPED
246.6MGOCONN @ MH 3 O'CLOCK/CAPPED
244DAGS
237.6TFOPEN
49CM
0MGOROACHES @ MH
2CM
0MWL
141.9TFC
246.6CM
246.6MGOCONN @ MH 9 O'CLOCK/CAPPED
100TFUNKNOWN
2DAGS
0MGOCONN @ MH 9 O'CLOCK/CAPPED
195TFC
244SSS
0MWM
0AMH18 0358
246MGOROACHES @ MH
2SSS
46.6TFOPEN
246.6AMH18 0357

Properties (7)

additional_info
630138051821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-19T00:31:39-07:00
documentation
PROPIPE
is_lateral_inspection
false