Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2021, 09:34 AM
  • 18 1232_18 1231_05182021_024754.mp4

Date
05/18/2021
W/O
890909
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01188
PipeID
P26191
Time
2:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8868
Sewer Name
18 EAST IMPERIAL HIGHWAY RELIEF TRUNK
City
SOUTH WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_890909_TV18137_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 1232
Downstream MH
18 1231
Dir. of Survey
Downstream
Length Surveyed
336.5 ft.
Total Length
336.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
132
Pipe schematic from manhole 18 1232 to 18 1231
MH: 18 1232MH: 18 1231downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 12320 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - POSSIBLE GREASE333 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - POSSIBLE GREASE336.5 ft. AMH - Downstream Manhole, Survey Ends - 18 1231

Observations (6)

DistanceCodeObservation
333DAGSPOSSIBLE GREASE
0AMH18 1232
2DAGSPOSSIBLE GREASE
336.5AMH18 1231
0MWM
0MWL

Properties (8)

additional_info
630138051721201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-05-18T02:34:19-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
40099