Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2021, 10:37 AM
  • 18 1229_18 0745_05182021_034552.mp4

Date
05/18/2021
W/O
890909
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01188
PipeID
P26188
Time
3:37 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8868
Sewer Name
18 EAST IMPERIAL HIGHWAY RELIEF TRUNK
City
SOUTH WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_890909_TV18137_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 1229
Downstream MH
18 0745
Dir. of Survey
Downstream
Length Surveyed
60.4 ft.
Total Length
60.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3A2A
O&M Rating
55
Overall Index
3
Overall Quick
Overall Rating
55
Pipe schematic from manhole 18 1229 to 18 0745
MH: 18 1229MH: 18 0745downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 12290 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - POSSIBLE GREASE DEPOSITS2.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start60.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - POSSIBLE GREASE DEPOSITS60.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK60.4 ft. AMH - Downstream Manhole, Survey Ends - 18 074560.4 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Settled Other,  15 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    2.9 ft. - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2.9DAGSPOSSIBLE GREASE DEPOSITS
0AMH18 1229
60.4MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0MWL
60.4AMH18 0745
2.9DSZ
60.4DSZ
60.3DAGSPOSSIBLE GREASE DEPOSITS

Properties (8)

additional_info
630138051721201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-05-18T03:37:12-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
40099