Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 06:15 AM
  • 18 0107_18 0106_05042021_233441.mp4

Date
05/04/2021
W/O
891153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13927
Time
11:15 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8860
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0107
Downstream MH
18 0106
Dir. of Survey
Downstream
Length Surveyed
310.6 ft.
Total Length
310.6 ft.
Structural Index
3
Structural Quick
423Q
Structural Rating
283
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
283
Pipe schematic from manhole 18 0107 to 18 0106
MH: 18 0107MH: 18 0106downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 18 01070 ft. MWL - Water Level, 20 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"11.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"52.2 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES56.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.8 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES108.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN112.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES144 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES156.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES160.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN163.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES186.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start209.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN212.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN213.9 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES258.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"261.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"310 ft. MGO - General Observation - ROACHES @ MH310.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish310.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0106

Observation photos (9)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    52.2 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    70.8 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    132 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    144 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    156.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    180.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    186.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    213.9 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
144FL
186.9FL
8TFA
212.5TFOPEN
2.3SAV
108.8TFOPEN
310.6SAV
310.6AMH18 0106
180.9FL
0MWM
0MGOCONN @ MH 3 O'CLOCK/OPEN
0AMH18 0107
59.9TFC
156.4CL
261.3TFC
112.1TFC
163.9TFC
213.9FM
0MWL
310MGOROACHES @ MH
11.2TFC
56.8TFC
258.1TFA
52.2FL
209.4TFOPEN
310.5FL
70.8FM
160.7TFOPEN
132FL

Properties (7)

additional_info
630074050421202
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-04T23:15:00-07:00
documentation
PROPIPE
is_lateral_inspection
false