Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 05:13 AM
  • 18 0105_18 0104_05062021_222547.mp4

Date
05/06/2021
W/O
891153
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13925
Time
10:13 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8847
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0105
Downstream MH
18 0104
Dir. of Survey
Downstream
Length Surveyed
170.5 ft.
Total Length
170.5 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
165
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
231
Pipe schematic from manhole 18 0105 to 18 0104
MH: 18 0105MH: 18 0104downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 01050 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"35.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8" - OPEN38 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 8" - OPEN65.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"68.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"117.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"120.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"167.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish168 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish168 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish170 ft. MGO - General Observation - ROACHES @ MH170.5 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED170.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0104170.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    38 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

Observations (22)

DistanceCodeObservation
0MGOCONN @ MH 9 O'CLOCK/
2DAGS
167.9SAV
68.4TFA
0MGOROACHES @ MH
170MGOROACHES @ MH
170.5MGOCONN @ MH 9 O'CLOCK/CAPPED
0AMH18 0105
170.5AMH18 0104
168SSS
38TBOPEN
120.6TFC
20.4TFC
65.2TFC
2SSS
35.4TFOPEN
0MWL
170.5MGOCONN @ MH 3 O'CLOCK/CAPPED
2.5SAV
117.2TFC
0MWM
168DAGS

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-06T22:13:43-07:00
documentation
PROPIPE
is_lateral_inspection
false