Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 05:27 AM
  • 18 0104_18 0103_05062021_224801.mp4

Date
05/06/2021
W/O
891153
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13924
Time
10:27 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8847
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0104
Downstream MH
18 0103
Dir. of Survey
Downstream
Length Surveyed
355.7 ft.
Total Length
355.7 ft.
Structural Index
2
Structural Quick
3M2N
Structural Rating
363
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
503
Pipe schematic from manhole 18 0104 to 18 0103
MH: 18 0104MH: 18 0103downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01042 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.7 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES65.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"68.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"76.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES88.3 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start101 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Finish117.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8" - OPEN120.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"166.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8" - OPEN168.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"198.2 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES217.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8" - OPEN221 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"269.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN272.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"318 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8" - OPEN321.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"353 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0103

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    57.7 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    76.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start

    88.3 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    198.2 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
272.1TFC
0MGOCONN @ MH 9 O'CLOCK/CAPPED
65.5TFC
353.1SAV
0MWM
198.2CL
68.6TFC
269.6TFOPEN
168.9TFC
2DAGS
321.1TFC
57.7CL
0MGOCONN @ MH 3 O'CLOCK/CAPPED
117.3TFOPEN
355.7AMH18 0103
0MWL
2SSS
221TFC
76.5CM
120.1TFC
88.3CL
166.2TFOPEN
318TFOPEN
2.1SAV
217.8TFOPEN
0AMH18 0104
353DAGS
353SSS
101CL

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-06T22:27:47-07:00
documentation
PROPIPE
is_lateral_inspection
false