Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 05:52 AM
  • 18 0103_18 0102_05062021_231330.mp4

Date
05/06/2021
W/O
891153
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13923
Time
10:52 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8847
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0103
Downstream MH
18 0102
Dir. of Survey
Downstream
Length Surveyed
354.6 ft.
Total Length
354.6 ft.
Structural Index
2
Structural Quick
3M2N
Structural Rating
360
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
500
Pipe schematic from manhole 18 0103 to 18 0102
MH: 18 0103MH: 18 0102downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01030 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 8"13.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"56.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN59.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"110.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"113.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"151.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES157.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES162.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN165.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"173 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES211.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 8" - OPEN211.5 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES214 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"259.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"262.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"282.4 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES311 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"314.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"344.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"347.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"352 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish352 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354 ft. MGO - General Observation - ROACHES @ MH354.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE354.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE354.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0102

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    151.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    157.6 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    173 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    211.5 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    282.4 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

Observations (34)

DistanceCodeObservation
311TFC
173CL
282.4CL
110.7TFC
347.3TFC
354MGOROACHES @ MH
157.6CL
2.1SAV
353.5SAV
56.3TFOPEN
211.5CL
214TFC
2DAGS
354.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
162.3TFOPEN
13.6TFC
354.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
352SSS
211.1TFOPEN
151.8CL
344.4TFC
262.5TFC
354.6AMH18 0102
113.9TFC
0AMH18 0103
352DAGS
0MWL
0MWM
2SSS
165.3TFC
59.4TFC
314.1TFC
10.6TFA
259.4TFC

Properties (6)

custom_field_three
AGGREGATE VISIBLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-06T22:52:03-07:00
documentation
PROPIPE
is_lateral_inspection
false