Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 06:41 AM
  • 18 0100_18 0099_05062021_234858.mp4

Date
05/06/2021
W/O
891153
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13920
Time
11:41 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8847
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0100
Downstream MH
18 0099
Dir. of Survey
Downstream
Length Surveyed
100 ft.
Total Length
100 ft.
Structural Index
3
Structural Quick
3G2C
Structural Rating
154
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
2
Overall Quick
Overall Rating
192
Pipe schematic from manhole 18 0100 to 18 0099
MH: 18 0100MH: 18 0099downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01002 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"10.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8" - OPEN53.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8" - OPEN56.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8" - OPEN70.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES86.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8" - OPEN98 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish98 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish98 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish98.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish100 ft. MGO - General Observation - ROACHES @ MH100 ft. AMH - Downstream Manhole, Survey Ends - 18 0099

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    70.5 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
56.2TFOPEN
100MGOROACHES @ MH
53.4TFOPEN
70.5CL
98.9SAV
98SSS
100AMH18 0099
2DAGS
2CM
2SSS
10.6TFOPEN
7.6TFC
0MWM
98CM
0MWL
2.2SAV
0AMH18 0100
98DAGS
86.8TFOPEN

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-06T23:41:13-07:00
documentation
PROPIPE
is_lateral_inspection
false