Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2021, 08:35 AM
  • 18 0088_18 0087_05102021_014550.mp4

Date
05/10/2021
W/O
891153
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13907
Time
1:35 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8848
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0088
Downstream MH
18 0087
Dir. of Survey
Downstream
Length Surveyed
224.2 ft.
Total Length
224.2 ft.
Structural Index
2
Structural Quick
3H2I
Structural Rating
230
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
326
Pipe schematic from manhole 18 0088 to 18 0087
MH: 18 0088MH: 18 0087downstream0 ft. MGO - General Observation - CONN @ MH 3 O'OCLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 00880 ft. MWL - Water Level, 20 % of cross sectional area0 ft. MWM - Water Mark, 25 % of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.1 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES10.1 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: YES10.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: YES30 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start38.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES51.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"57 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish151.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"222 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish222 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224 ft. MGO - General Observation - ROACHES @ MH224.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0087224.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 11 o'clock,  , within 8 inches of joint: YES

    7.1 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock,  , within 8 inches of joint: YES

    10.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock,  , within 8 inches of joint: YES

    38.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
2.7SAV
151.9TFC
0MGOCONN @ MH 3 O'OCLOCK/ACTIVE
0AMH18 0088
0MWL
2SSS
51.2TFC
0MWM
57MWLS
224MGOROACHES @ MH
7.1DAE
224.2AMH18 0087
222DAGS
224.2SAV
222SSS
30MWLS
10.1DAR
10.1DAE
2DAGS
38.1DAE

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-10T01:35:14-07:00
documentation
PROPIPE
is_lateral_inspection
false