Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2021, 07:47 AM
  • 18 0084_18 0083_05132021_011639.mp4

Date
05/13/2021
W/O
891153
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13903
Time
12:47 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8864
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0084
Downstream MH
18 0083
Dir. of Survey
Downstream
Length Surveyed
385.2 ft.
Total Length
385.2 ft.
Structural Index
3
Structural Quick
4134
Structural Rating
16
O&M Index
2
O&M Quick
2N11
O&M Rating
153
Overall Index
2
Overall Quick
Overall Rating
169
Pipe schematic from manhole 18 0084 to 18 0083
MH: 18 0084MH: 18 0083downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00840 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"13.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES85.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"88.9 ft. TS - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN157.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN167.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES277.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"296 ft. RFJ - Roots Fine Joint, from 08 to 01 o'clock, within 8 inches of joint: YES344.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN378.7 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES383 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish385 ft. MGO - General Observation - ROACHES @ MH385.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish385.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0083

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    13.9 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    88.9 ft. - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    167.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    378.7 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
385MGOROACHES @ MH
13.9FL
3.1SAV
167.9FM
8.4TFA
385.2SAV
344.2TFOPEN
0AMH18 0084
0MGOROACHES @ MH
383DAGS
88.9TSOPEN
85.1TFC
296RFJ
0MWM
2DAGS
385.2AMH18 0083
157.1TFOPEN
378.7CM
0MWL
277.6TFA

Properties (7)

additional_info
630138051221202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-13T00:47:16-07:00
documentation
PROPIPE
is_lateral_inspection
false