Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2021, 04:51 AM
  • 18 0083_18 0082_05102021_220836.mp4

Date
05/10/2021
W/O
891398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13902
Time
9:51 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8861
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891153_TV18177_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0083
Downstream MH
18 0082
Dir. of Survey
Downstream
Length Surveyed
384.5 ft.
Total Length
384.5 ft.
Structural Index
2
Structural Quick
322N
Structural Rating
159
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
311
Pipe schematic from manhole 18 0083 to 18 0082
MH: 18 0083MH: 18 0082downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00830 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN104 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"153.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN180.1 ft. CC - Crack Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES246.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN250 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"307.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN382 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish382 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish383.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish383.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE384.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0082

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES

    180.1 ft. - Crack Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
0AMH18 0083
382DAGS
104TFA
2SSS
0MGOROACHES @ MH
384.5AMH18 0082
153.4TFOPEN
383.6SAV
0MWL
246.6TFOPEN
15.8TFOPEN
2.1SAV
0MWM
383.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
250TFC
382SSS
180.1CC
2DAGS
307.1TFOPEN

Properties (7)

additional_info
630138051021201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-10T21:51:27-07:00
documentation
PROPIPE
is_lateral_inspection
false