Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 20, 2021, 05:42 AM
  • 18 0834_18 0833_05192021_225125.mp4

Date
05/19/2021
W/O
890885
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00708
PipeID
P14697
Time
10:42 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8872
Sewer Name
18 SO WHITTIER OUTFALL TR, SECT 6
City
SANTA FE SPRINGS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
WO_890885_TV18110_MAY2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0833
Downstream MH
18 0834
Dir. of Survey
Upstream
Length Surveyed
296.1 ft.
Total Length
296.1 ft.
Structural Index
3
Structural Quick
524G
Structural Rating
468
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
3
Overall Quick
Overall Rating
584
Pipe schematic from manhole 18 0833 to 18 0834
MH: 18 0833MH: 18 0834upstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Ends - 18 08342.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish12.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES42.1 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish43.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish49.2 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES, Start249.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start294.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start294.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start294.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start296.1 ft. MWL - Water Level, 20 %of cross sectional area296.1 ft. MWM - Water Mark, 25 %of cross sectional area296.1 ft. AMH - Downstream Manhole, Survey Begins - 18 0833

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    46.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    246.9 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
246.9B
46.8FM
294SSS
253FM
0MWL
0MWM
296.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
294CM
294DAGS
254B
2CM
2DAGS
0AMH18 0833
283.5FM
296.1AMH18 0834
2SSS

Properties (7)

additional_info
630138051921202
custom_field_three
MULTIPLE FRACTURES/BROKEN PIPE
custom_field_two
2
customer
1
datetime
2021-05-19T22:42:33-07:00
documentation
PROPIPE
is_lateral_inspection
false