Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2021, 08:53 AM
  • H 0550_H 0549_05212021_020903.mp4

Date
05/21/2021
W/O
890865
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00185
PipeID
P10974
Time
1:53 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8922
Sewer Name
H JOINT OUTFALL H - UNIT 8B
City
BALDWIN PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_890865_TV15169_MAY2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0550
Downstream MH
H 0549
Dir. of Survey
Downstream
Length Surveyed
297.1 ft.
Total Length
297.1 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
295
O&M Index
2
O&M Quick
412K
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
417
Pipe schematic from manhole H 0550 to H 0549
MH: H 0550MH: H 0549downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05500 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MGO - General Observation - 70% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start41.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"69.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN93 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN149 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN153.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"157.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN204.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN213.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"229 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"237.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"295 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish296.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish296.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish297.1 ft. AMH - Downstream Manhole, Survey Ends - H 0549297.1 ft. MGO - General Observation - ROACHES @ MH297.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN

Observation photos (4)

  • General Observation - 70% MAG COAT

    2 ft. - General Observation - 70% MAG COAT

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    297.1 ft. - General Observation - ROACHES @ MH

Observations (23)

DistanceCodeObservation
69.6TFOPEN
41.5TFA
213.2TFC
237.1TFC
295SSS
153.8TBA
157.2TFOPEN
2MGO70% MAG COAT
297.1AMHH 0549
0MWL
296.1SAV
93TFUNKNOWN
2SSS
0AMHH 0550
2SAV
0MWM
297.1MGOROACHES @ MH
204.9TFOPEN
149TFUNKNOWN
229TFC
2DAGS
297.1MGOCONN @ MH 9 O'CLOCK/UNKNOWN
296.1DAGS

Properties (7)

additional_info
630069052021202
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2021-05-21T01:53:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false