Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2021, 08:54 AM
  • 18 0067_18 0066_05112021_020855.mp4

Date
05/11/2021
W/O
891398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13881
Time
1:54 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8862
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0067
Downstream MH
18 0066
Dir. of Survey
Downstream
Length Surveyed
251.1 ft.
Total Length
251.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0067 to 18 0066
MH: 18 0067MH: 18 0066downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00670 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start161 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"251.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0066251.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
251.1AMH18 0066
2.1SAV
0AMH18 0067
161TF
0MWM
0MWL
251.1SAV
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630138051021202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-11T01:54:59-07:00
documentation
PROPIPE
is_lateral_inspection
false