Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 04:56 AM
  • 18 0106_18 0105_05062021_220944.mp4

Date
05/06/2021
W/O
891398
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13926
Time
9:56 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8846
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0106
Downstream MH
18 0105
Dir. of Survey
Downstream
Length Surveyed
133.9 ft.
Total Length
134 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0106 to 18 0105
MH: 18 0106MH: 18 0105downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01060 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES10.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 8"13.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8"50 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"53 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8"102 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"105.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"132.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish134 ft. AMH - Downstream Manhole, Survey Ends - 18 0105134 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    6.1 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
53TF
6.1CL
102TFC
50TFC
0MWM
0AMH18 0106
0MWL
105.2TFC
134AMH18 0105
10.3TF
132.2SAV
13.2TF
134MGOCONNECTION AT MH 9 O'CLOCK
2.1SAV

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-06T21:56:32-07:00
documentation
PROPIPE
is_lateral_inspection
false