Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 08:15 AM
  • 18 0099_18 0098_05072021_012835.mp4

Date
05/07/2021
W/O
891398
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13919
Time
1:15 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8846
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0099
Downstream MH
18 0098
Dir. of Survey
Downstream
Length Surveyed
194.3 ft.
Total Length
194.3 ft.
Structural Index
3
Structural Quick
3422
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 18 0099 to 18 0098
MH: 18 0099MH: 18 0098downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00990 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - PIPE IS VCP24 ft. CM - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES40.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"61.2 ft. IS - Infiltration Stain, at 09 o'clock, within 8 inches of joint: YES61.2 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES63.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"101 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"102 ft. CS - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES102 ft. IS - Infiltration Stain, at 08 o'clock, within 8 inches of joint: YES128.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"160.4 ft. FS - Fracture Spiral, from 03 to 09 o'clock, within 8 inches of joint: YES170.2 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES180.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES187.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"194.3 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK194.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0098

Observation photos (9)

  • General Observation - PIPE IS VCP

    2 ft. - General Observation - PIPE IS VCP

  • Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    24 ft. - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, at 09 o'clock, within 8 inches of joint: YES

    61.2 ft. - Infiltration Stain, at 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    61.2 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    102 ft. - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, at 08 o'clock, within 8 inches of joint: YES

    102 ft. - Infiltration Stain, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 03 to 09 o'clock, within 8 inches of joint: YES

    160.4 ft. - Fracture Spiral, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    170.2 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    180.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
24CM
102CS
194.3MGOCONNECTION AT MH 12 O'CLOCK
187.1TF
128.9TF
40.2TF
0MWM
63.4TF
0AMH18 0099
160.4FS
61.2IS
0MWL
180.8CM
194.3AMH18 0098
170.2CM
61.2CS
101TF
102IS
2MGOPIPE IS VCP

Properties (6)

custom_field_three
CRACKS, FRACTURES
custom_field_two
3
customer
1
datetime
2021-05-07T01:15:28-07:00
documentation
PROPIPE
is_lateral_inspection
false