Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 07:43 AM
  • 18 0098_18 0097_05072021_005049.mp4

Date
05/07/2021
W/O
891398
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13918
Time
12:43 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8846
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0098
Downstream MH
18 0097
Dir. of Survey
Downstream
Length Surveyed
110.7 ft.
Total Length
110.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0098 to 18 0097
MH: 18 0098MH: 18 0097downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 00980 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - PIPE IS VCP16.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start44.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"48 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"100 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES104.8 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES110.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0097110.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (4)

  • General Observation - PIPE IS VCP

    2 ft. - General Observation - PIPE IS VCP

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    16.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    100 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    104.8 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
110.7AMH18 0097
0MGOCONNECTION AT MH 3 O'CLOCK
48TF
44.5TF
0AMH18 0098
100FL
0MWM
110.7DAGS
16.2DAGS
104.8FS
2MGOPIPE IS VCP
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL

Properties (6)

custom_field_three
FRACTURES
custom_field_two
3
customer
1
datetime
2021-05-07T00:43:18-07:00
documentation
PROPIPE
is_lateral_inspection
false