Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 09:09 AM
  • 18 0096_18 0095_05072021_022436.mp4

Date
05/07/2021
W/O
891398
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13916
Time
2:09 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8846
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0095
Downstream MH
18 0096
Dir. of Survey
Upstream
Length Surveyed
285.9 ft.
Total Length
285.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0095 to 18 0096
MH: 18 0095MH: 18 0096upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00960 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish182.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 8"282.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start285.9 ft. MWM - Water Mark, 35 %of cross sectional area285.9 ft. AMH - Downstream Manhole, Survey Begins - 18 0095285.9 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    103.7 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 8"

Observations (7)

DistanceCodeObservation
0MWM
0AMH18 0095
3.1SAV
285.9AMH18 0096
103.7TBA
0MWL
285.9SAV

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-07T02:09:36-07:00
documentation
PROPIPE
is_lateral_inspection
false