Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2021, 08:56 AM
  • 18 0095_18 0094_05072021_020840.mp4

Date
05/07/2021
W/O
891398
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13915
Time
1:56 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8846
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
18 0094
Downstream MH
18 0095
Dir. of Survey
Upstream
Length Surveyed
288.6 ft.
Total Length
288.6 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0094 to 18 0095
MH: 18 0094MH: 18 0095upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00950 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"135.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"169.1 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: NO200 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"286.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start288.6 ft. MWM - Water Mark, 35 %of cross sectional area288.6 ft. AMH - Downstream Manhole, Survey Begins - 18 0094288.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK288.6 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    88.6 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: NO

    119.5 ft. - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: NO

Observations (11)

DistanceCodeObservation
288.6AMH18 0095
288.6SAV
119.5CC
0MWM
0AMH18 0094
88.6TB
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
280.9TFC
2SAV
152.9TFC

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-07T01:56:16-07:00
documentation
PROPIPE
is_lateral_inspection
false