Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2021, 11:02 AM
  • 18 0090_18 0089_05102021_041814.mp4

Date
05/10/2021
W/O
891398
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00698
PipeID
P13909
Time
4:02 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8849
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0090
Downstream MH
18 0089
Dir. of Survey
Downstream
Length Surveyed
354 ft.
Total Length
354 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0090 to 18 0089
MH: 18 0090MH: 18 0089downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00900 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES100.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"198.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 8"316.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"350.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354 ft. AMH - Downstream Manhole, Survey Ends - 18 0089

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    29.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
316.2TFC
0AMH18 0090
100.7TFC
354AMH18 0089
2.8SAV
0MWM
29.9CL
350.6SAV
198.2TF
0MWL

Properties (6)

custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-05-10T04:02:00-07:00
documentation
PROPIPE
is_lateral_inspection
false