Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 09:07 AM
  • 18 0117_18 0116_05052021_022326.mp4

Date
05/05/2021
W/O
891398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13937
Time
2:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8859
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0117
Downstream MH
18 0116
Dir. of Survey
Downstream
Length Surveyed
356.6 ft.
Total Length
356.6 ft.
Structural Index
3
Structural Quick
3[00
Structural Rating
423
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
425
Pipe schematic from manhole 18 0117 to 18 0116
MH: 18 0117MH: 18 0116downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01173 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start44.6 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES60.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.1 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES210.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"310.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"356.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0116356.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK356.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES

    175.1 ft. - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
161.5TF
262TF
356.6AMH18 0116
167.7TFC
216.5TFC
316.9TFC
67.2TFC
268.3TFC
356.6SAV
7.9CM
175.1RFJ
310.7TFC
60.8TF
210.3TFC
44.6RFJ
0MWM
356.6MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
0AMH18 0117
109.9TF
115.9TFC
356.6CM
3SAV

Properties (7)

additional_info
630074050421201
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-05T02:07:59-07:00
documentation
PROPIPE
is_lateral_inspection
false