Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 04:55 AM
  • 18 0112_18 0111_05042021_220043.mp4

Date
05/04/2021
W/O
891398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13932
Time
9:55 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8859
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_891398_TV18083_MAY2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0112
Downstream MH
18 0111
Dir. of Survey
Downstream
Length Surveyed
58.6 ft.
Total Length
58.6 ft.
Structural Index
3
Structural Quick
3B21
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 18 0112 to 18 0111
MH: 18 0112MH: 18 0111downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01120 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"12.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"20.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES27 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES36.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES43.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"49.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK58.6 ft. AMH - Downstream Manhole, Survey Ends - 18 011158.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    20.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    27 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    36.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
6.8TF
58.6MGOCONNECTION AT THE MH 3 OC'LOCK
0AMH18 0112
58.6AMH18 0111
43.4TFC
49.5TFC
0MWL
20.9CL
0MWM
2.1SAV
36.1FL
27FL
58.6SAV
12.9TFC

Properties (7)

additional_info
630074050421201
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-05-04T21:55:18-07:00
documentation
PROPIPE
is_lateral_inspection
false